Combined Footing Analysis Calculator

Analyse a footing that carries two columns. Quick Structural treats the footing as an inverted beam loaded by the soil pressure, and gives you the shear forces, the longitudinal and transverse bending moments and the diagrams.

What the combined footing analysis does

The footing is analysed as an inverted beam. The soil pressure under the footing acts as an upward line load, and the two column loads act downward. From these the report finds the shear force and bending moment at every key point, the position of zero shear, and the bending in the transverse direction at the column face.

Example: two columns on one footing

These are the inputs and results from the report shown below. The footing is 4.60 m long and 2.3 m wide.

Soil pressure377 kN/m²
Footing width and lengthB = 2.3 m, L = 4.60 m
Equivalent line load867.10 kN/m
Column loadsLeft 1650 kN (300 × 300 mm), right 2340 kN (400 × 400 mm)
LayoutLeft overhang 0.54 m, spacing 3.0 m, right overhang 1.06 m
Largest shear force1420 kN
Moment at the left column126 kNm
Moment at the right column483 kNm
Peak moment between the columns679 kNm at 1.903 m from the left edge
Transverse moment188 kNm per metre, from a projection of 1.0 m

A real combined footing analysis report

This is the report exactly as Quick Structural produces it. It includes the plan view, the shear and moment tables and the diagrams.

Open the full report as a PDF

Frequently asked questions

Why is a combined footing analysed as an inverted beam?

The soil pressure pushes up on the footing and the columns push down, so the footing bends like a beam loaded upside down. The same shear force and bending moment methods apply.

What is the transverse bending moment?

It is the bending across the width of the footing, found for a one metre strip at the face of the column where the projection acts as a cantilever.

Can I then design the footing?

Yes. Use the moments and shears in the combined footing design to find the reinforcement and run the punching shear checks.

Is there a simpler option for one column?

Yes. The isolated footing design handles a single column.

Can I rely on the results for a real building?

Quick Structural is a design aid. Every design should be checked and approved by a qualified, registered engineer before it is used for construction.